AC input 180~264VAC only130% peak load capability1 10mm slim design Built-in active PFC function compliance to EN61000-3-2 High efficiency 94% and low power dissipation
AC input 180~264VAC only130% peak load capability1 10mm slim design Built-in active PFC function compliance to EN61000-3-2 High efficiency 94% and low power dissipation
Features
● AC input 180~264VAC only
● 130% peak load capability
● 110mm slim design
● Built-in active PFC function compliance to EN61000-3-2
● High efficiency 94% and low power dissipation
● Protections: Short circuit /Overload/Over voltage /Over temperature
● Cooling by free air convection
● Built-in constant current limiting circuit
● Can be installed on DIN rail TS-35/7.5 or 15
● UL508(industrial control equipment)approved
● EN61000-6-2(EN50082-2)industrial immunity level
● Current sharing up to 3840W(3+1)
● Built-in DC OK relay contact
● 100% full load burn-in test
● 3 years warranty
MODEL |
SDR-960-24 |
SDR-960-48 |
|
OUTPUT |
DC VOLTAGE |
24V |
48V |
RATED CURRENT |
40A |
20A |
|
CURRENT RANGE |
0 ~ 40A |
0 ~ 20A |
|
RATED POWER |
960W |
960W |
|
PEAK CURRENT |
52A |
26A |
|
PEAK POWER Note.6 |
1248W (3sec.) |
||
RIPPLE & NOISE (max.) Note.2 |
180mVp-p |
250mVp-p |
|
VOLTAGE ADJ. RANGE |
24 ~ 28V |
48 ~ 55V |
|
VOLTAGE TOLERANCE Note.3 |
±1.0% |
±1.0% |
|
LINE REGULATION |
±0.5% |
±0.5% |
|
LOAD REGULATION |
±1.0% |
±1.0% |
|
SETUP, RISE TIME |
1000ms, 100ms/230VAC at full load |
||
HOLD UP TIME (Typ.) |
14ms / 230VAC at full load |
||
INPUT |
VOLTAGE RANGE Note.7 |
180 ~ 264VAC 254 ~ 370VDC |
|
FREQUENCY RANGE |
47 ~ 63Hz |
||
POWER FACTOR (Typ.) |
PF≥0.95/230VAC at full load |
||
EFFICIENCY (Typ.) |
94% |
94% |
|
AC CURRENT (Typ.) |
6A/230VAC |
||
INRUSH CURRENT (Typ.) |
COLD START 50A / 230VAC |
||
LEAKAGE CURRENT |
<3.5mA / 240VAC |
||
PROTECTION |
OVERLOAD |
Normally works within 105 ~ 130% rated output power for more than 3 seconds and then shutdown o/p voltage with auto-recovery after 30 seconds if the peak load condition is removed |
|
Constant current limiting within 130 ~ 150% rated output power for more than 3 seconds and then shutdown o/p voltage, re-power on to recover |
|||
OVER VOLTAGE |
29 ~ 33V |
56 ~ 65V |
|
Protection type : Shutdown o/p voltage, with auto-recovery or re-power on to recover |
|||
OVER TEMPERATURE |
Shutdown o/p voltage, recovers automatically after temperature goes down |
||
FUNCTION |
DC OK REALY CONTACT RATINGS (max.) |
60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5Aresistive load |
|
CURRENT SHARING |
Please refer to function manual |
||
ENVIRONMENT |
WORKING TEMP. Note.5 |
-30 ~ +70℃ (Refer to "Derating Curve") |
|
WORKING HUMIDITY |
20 ~ 95% RH non-condensing |
||
STORAGE TEMP., HUMIDITY |
-40 ~ +85℃ , 10 ~ 95% RH non-condensing |
||
TEMP. COEFFICIENT |
±0.03%/℃ (0 ~ 50℃) |
||
VIBRATION |
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,Y, Z axes; Mounting: Compliance to IEC60068-2-6 |
||
SAFETY & EMC (Note 4) |
SAFETY STARDS |
UL508,TUV EN62368-1 , BSMI CNS14336-1, AS/NZS62368.1 , EACTPTC 004 approved ; (meet EN60204-1) |
|
WITHST VOLTAGE |
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC |
||
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH |
||
EMC EMISSION Note.8 |
Compliance to EN55032 (CISPR32), EN61204-3 Conduction class B, Radiation class A, EN61000-3-2,-3, EACTPTC 020, BSMI CNS13438 |
||
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, EACTPTC 020 |
||
OTHERS |
MTBF |
69.8K hrs min. MIL-HDBK-217F (25℃) |
|
DIMENSION |
110*125.2*150mm (W*H*D) |
||
PACKING |
2.47Kg ; 6pcs/15.8Kg/1.55CUFT |
||
NOTE |
1. AII parameters NoT speciaIIy mentioned are measured at 230VAC input, rated Ioad and 25℃ of ambient temperature. 2. RippIe & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf paraIIeI capacitor. 3. ToIerance : incIudes set up toIerance, Iine reguIation and Ioad reguIation. 4. The power suppIy is considered a component which wiII be instaIIed into a finaI equipment. The finaI equipment must be re-confirmed that it stiII meets EMC directives. 5. InstaIIation cIearances : 40mm on top, 20mm on the bottom, 5mm on the Ieft and right side are recommended when Ioaded permanentIy with fuII power. In case the adjacent device is a heat source, 15mm cIearance is recommended. 6. 3 seconds peak power max. and the average output power shouId not exceed the rate power. 7. Derating may be needed under Iow input voItage. PIease check the derating curve for more detaiIs. 8. ConsuIt MEAN WELL for depIoyment of Radiation cIass B. 9. The ambient temperature derating of 3.5℃ ℃/1000mwithfanIessmodeIsandof5/1000m with fan modeIs for operating aItitude higher than 2000m(6500ft). ※ Product LiabiIity DiscIaimer :For detaiIed information, pIease refer to https://www.meanwell.com/serviceDisclaimer.aspx |
Ordering Information |
---|
Date | Version | Description | Download |
---|---|---|---|
2024-09-18 | V1.0 | 960W Single Output Industrial DIN RAIL with PFC Function | |
Photo | Model | Description |
---|